HYG-108 kVA/108 kV series resonant AC voltage withstanding test device

RELEVANT RECOMMENDATIONS
-
VIDEO CONTENTS
1. The test equipment should be used by high-pressure test professionals. Before use, the instructions should be carefully read and trained repeatedly.
2. Operators should be no less than 2 persons. When using, the safety operation rules of the high-pressure test of the unit shall be strictly observed.
3. In order to ensure the safety and correctness of the test, besides being familiar with the product instructions, the test operation must be carried out strictly in accordance with the relevant national standards and regulations.
4. Connections should not be misconnected, otherwise the test device may be damaged.
5. When the device is used, the output voltage is high or ultra-high voltage. It must be grounded reliably and the operation safety should be paid attention to.
-
TEST EQUIPMENT LISTS
1. Frequency conversion power supply 1:
Rated power: 6kW;
Input voltage: single-phase 380V + 10% 45-65Hz
Output voltage: 0-400V adjustable
Output Voltage Frequency: 30-300 Hz
0.1Hz step adjustable
Frequency instability < 0.02%
Output current: 0-15A
2. High Voltage Reactors (4 sets): 27kV/1A
Rated operating voltage: 27kV
Rated working current: 1A
Rated inductance: 96H
Continuous working hours: 60 minutes
Temperature rise: less than 60 degrees
Working frequency: 30-300 Hz
3. Incentive change into one:
Rated capacity: 6kVA
Input voltage: 400V
Output voltage: 1.5KV/3KV/5KV, 1.5KV for 10KV, 3km under cable withstand voltage test; 3KV for 35KV cable, 1KV, 10KV substation system withstand voltage test; 5KV for 35KV substation system withstand voltage test.
4. Capacitance divider: 110kV pure capacitance type:
Self-capacitance: 1000pF
Working frequency: 30-300 Hz
Uncertainty: 1.5%
Rated voltage: 110 kV/1000pF
-
INSTRUCTIONS
Use the appropriate power cord: Only the power cord which is special for this product and meets the specifications of this product can be used.
Connect and disconnect correctly: When the test wire is connected to the live terminal, do not connect or disconnect the test wire at will.
Product grounding: In addition to grounding through power line grounding wire, the grounding column of the product shell must be grounded. In order to prevent electric shocks, grounding conductors must be connected to the ground. Before connecting with the input or output terminals of the product, it should be ensured that the product is properly grounded.
Note all terminal ratings: In order to prevent fire or shock hazards, please pay attention to all ratings and markings of this product. Before connecting this product, please read the instructions for the use of this product in order to get more information about the rated value.
Do not operate without instrument cover: If the cover or panel has been removed, do not operate this product.
Do not operate in case of suspected faults: If the product is suspected to be damaged, the company's maintenance personnel should check and do not continue to operate.
Do not operate in humid environment
Do not operate in a violent environment
Keep product surface clean and dry